Permit Number: T02CM05372
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM05372
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
11/20/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/26/2002 JIM EGAN FIRE REVIEW Approved
12/12/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approv-Cond
12/19/2002 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Approved
12/19/2002 MARTIN HAEBERLE WATER REVIEW Approved
12/23/2002 GERRY KOZIOL WWM REVIEW Approved
12/23/2002 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

GLOBAL: CLARIFY WHICH PHASE IS INCLUDED IN THIS SUBMITTAL. ELECTRICAL STATES 2A BUT COVER SHEET STATES 2B. SEE ANNOTATIONS ON SHEETS BE0.1, BE1.1, AND BE1.3.
Sheet BE1.3
1. Enlarged Electrical Room SP-6. New 75 KVA suspended needs detail to enable evaluation of proper equipment clearances and installation per NEC 450-13 (b), and Article 110. Need structural design and calculations as well.

Sheet BE2.10
Grid 28/P two runs are indicated for Panel EH7 Circuits 1,3,5. Based on the panel schedule it appears that one of those runs should go to Panel EH7 Circuits 2,4,6.

Sheet BE6.2
1. Show connection to grounding electrode system from new transformer XO terminal.

2. No neutral wire is indicated going to food kiosk. Correct as necessary.

Specifications
16460, 3.1. Also must bond to the building's water system.
12/27/2002 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Approved Provide a fixture count for building drain serving the new utility box.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2003 LISA LESNY OUT TO CUSTOMER Completed