Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM05370
Parcel: 106030720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05370
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. An additional cleanout is required for the building sewer (every 100 feet or aggregate change in direction of 135 degrees). Reference Section 719.1, UPC 1994.
2. The wall box shown on Unit #3 Stack Diagram requires a trap and vent. Clarify how the T&P relief from the water heater in Unit #3 is to be piped. Show how the clean out for P-3 will be handled on Units 2 and 5. Revise the piping layout for P-4 to match the plumbing plan and the detail on P2. Reference Section 302.3, Uniform Administrative Code, 1997.
3. Revise the connection of the waste line from Unit 6 to the building sewer to have the correct relationship with the direction of flow. Reference Section 311.7, UPC 1994.
4. Clarify the routing of the building drains from Units #2 and #5.
5. Modify the drawings (First Floor Plumbing Plan and Unit #5 Stack Diagram) delete the backwater valves. Reference Section 710.1, UPC 1994.
6. Second floor building drain clean out is required per Sections 707.4 and 707.5, UPC 1994, as amended by the State of Arizona. Revise drawing as required.
7. Comment not addressed. If the water heater (WH-1) is not supplied with integral heat traps, provide heat traps as required by Section 504.9, IECC 1998.
02/13/2004 DAVID RIVERA ZONING REVIEW Approved
02/17/2004 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Passed
12/09/2003 Blanca Espino ENGINEERING REVIEW Approved
12/12/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The envelope designer has not signed the compliance statement of the Energy Code analysis.