Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM05370
Parcel: 106030720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05370
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2003 GERRY KOZIOL WWM REVIEW Denied Needs to show location/method of connection to public sewer
06/13/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show sizes and routes of condensate drains on plans.
2. The Model Energy Code analysis supplied does not provide enough information to demonstrate compliance to Section 502.2.2 or Section 502.2.3, IECC 1998.
3. Provide HVAC load calculations. Reference Section 503.3.1, IECC 1998.
06/13/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the size and routing of water and sewer lines, the slope of the sewer lines, and the location of clean outs on the site plan. Coordinate the site plan with the plumbing plans. Reference Section 302.3, Uniform Administrative Code, 1997.
2. Coordinate Unit #3 Stack Diagram with 1st floor plumbing plan; clean out for P-3 not shown on riser diagram. Show how clean out will be handled on Units 2 and 5. Reference Section 302.3, Uniform Administrative Code, 1997.
3. Show how the clean outs for P-3 and P-3A (Units 4 and 6) are readily accessible. Reference Section 707.9, UPC.
4. Coordinate 1st Floor Riser Diagram with Detail A/P3. Diagram shows expansion tank connected to hot water; the equipment listing requires connection to cold water. Reference Section 301.2, UPC 1994.
5. Revise ambiguous pipe sizes shown on 1st Floor Riser Diagram. Sizes should reflect the results of the water calculations as modified to restrict the water velocities as noted in Section A 6.1 and UPC 1994 and Section 610.0, IAPMO Installation Standard 3-93.
6. The 4" waste line from Unit #5 is shown as running "in the joist space". Provide details and structural calculations. Reference Section 302.3, Uniform Administrative Code, 1997.
7. Confirm need for backwater valves. Note 11 indicates backwater valves are not needed. Reference Section 710.1, UPC 1994.
8. Provide detail to show how the dishwasher (P-6) connection conforms to Section 807.4, UPC 1994, as amended by the State of Arizona. Revise drawing as required.
9. Second floor building drain clean out is required per Section 707.4, UPC 1994, as amended by the State of Arizona. Revise drawing as required.
10. Show routing of P/T relief pipes from water heaters. Reference Section 302.3, Uniform Administrative Code, 1997.
11. If the water heater (WH-1) is not supplied with integral heat traps, provide heat traps as required by Section 504.9, IECC 1998.
06/20/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide a detail of the drop ceiling in relation to the vertical and horizontal fire assemblies. Detail did not include how vertical fire assemblies are to be maintained through ceiling drops. i.e. kitchen drops
2. Provide details for accessible features for the Type A unit. Unit does not comply with requirements per Chapter 10 of ANSI 117.1. Revise plans and provide details.
3. All units on the first floor to be Type B units except the one Type A unit. Revise plans and provide specifications and details. Reference section 1107.5 IBC. Provide details and specify which units are to be Type B units. Further reference is Chapter 10 ANSI 117.1
4. New comment. Chase detail does not reflect the variation of chase location from the first floor to the second floor. Please clarify
07/03/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

1. "Small appliance branch circuits shall not serve any other loads per NEC 210-52 (b) (2). Reconfigure kitchen branch circuits." The above comment was on the first submittal. For example, in Unit One on the first floor, there is exterior lighting, interior lighting, and an exterior receptacle on the Dining Room Circuit A-17; . A Kitchen Countertop GFI is on Circuit A-9, primarily used for lighting. Make corrections typical for all units.
2. "Bathroom branch circuits shall not serve any other loads per NEC 210-11 (c) (3). Reconfigure bathroom branch circuits." The above comment was on the first submittal. Suggest moving the GFI receptacle by the sink from Circuit A-7, which also serves the Bedroom, to A-5. Make corrections typical for all units.
3. Lighting fixture A3 is does not appear to be appropriate for exterior installation. Lighting schedules does not indicate suitability for wet/damp location. No fixture cut sheet.
4. Lighting fixture A3 does not appear to meet the requirements of the Lighting Ordinance. This wattage of lamp shall have full cutoff light distribution of luminaire.
5. Fixture S3 needs to be changed. No incandescent lighting permitted. Per the 1998 IECC, Section 705.5, exterior lighting shall have a source efficiency of at least 45 lumens per watt.
6. "Countertop and outdoor receptacles shall be GFCI per NEC 210-8 (a) (3) and (6)." Add receptacles on Circuit 11 to this requirement.
7. Service load, at 392.34 amps, exceeds 600 kcmil aluminum conductor ampacity, which is 340 amps according to the 75ÂșC column of Table 310-16.
8. No equipment grounding conductor shall be installed in conduit with service entrance conductors. This applies to the conduit run on the line side of the service disconnect.
9. The equipment grounding conductors from the gutter to the meters, and from the meters to the panel disconnects, need to be sized according to the overcurrent device ahead of them, but in no case shall be larger than the circuit conductors. Thus they are all undersized per NEC 250-122 (a). Correct, and re-evaluate conduit fill.
07/14/2003 Joseph Linville ZONING REVIEW Denied Zoning
7/15/2003
Building plans may not be reviewed and approved until the site plan is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/15/2003 ANGIE SHOFFSTALL REJECT SHELF Completed