Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM05370
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2003 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning will approve building plans after approval of the building plans has been given by the structural (commercial) reviewers. An approved site plan is also required prior approval of the building plans. |
| 01/08/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide cross section of how hold-downs are to be installed at the second floor. 2. Specify anchoring embeddedment and configuration of hold-downs. Reference manufacturer installation criteria. 3. Provide a stairway detail. 4. Provide handrail extensions as per section 1003.3.11.5 IBC 5. Show on plans a complete column detail including foundation anchoring methods, load path connections and attachments. 6. Provide a detail of the drop ceiling in relation to the vertical and horizontal fire assemblies. 7. Fire assemblies listed reference the UBC. Revise plans to reflect assemblies under the 2000 IBC. 8. Screening of attic vents required per section 1202 IBC. note on plans 9. Two layers of underlayment required for asphalt shingle less than 4/12 pitch. Plans indicate one layer. Revise plans. Table 1507.2 IBC 10. An attic access is required for each attic area. Show location on plans. Reference section 1208 IBC 11. Include structural calculations for stairs. Note to be designed using a minimum of 100 pound per square foot floor load. Reference Table 1607.1 IBC. 12. Indicate on plan header sizes and locations. Include calculations for beams being used. 13. Provide details and structural calculations for deck anchorage. Reference section 1604.8.3 IBC. 14. Use current adopted code for structural calculations. Calculations indicate 91 NDS. 15.Dwelling live loads to be used are 40 lbs. per square foot not 20. Revise plans. Reference Table 1607.1 IBC. 16.Provide structural calculations and referenced geotechnical report for building foundations. 17. Provide hangar types to be used. See sheet A9. 18. Provide details for accessible features for the Type A unit 19. All units on the first floor to be Type B units except the one Type A unit. Revise plans and provide specifications and details. Reference section 1107.5 IBC. 20. Detail on plans required signage for the accessible parking space. 21. Provide cross elevations for ramps and loading areas. 22. Deferred submittals require approval of the building official. Submit request to David Mann, P.E. Building Official City of Tucson with proposed time of deferred submittal. |
| 01/08/2003 | MARTIN HAEBERLE | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Site plan needs to include building sewer, elevations of manholes, gas, and water. 2. Provide second floor plumbing plan and isometric. 3. Building sewer ran parallel in footing requires structural design. Provide details and calculations. 4. Provide method and details of wall/ floor fire assemblies' penetrations. 5. Backwater valve to be installed for fixtures located below the elevation of the next upstream manhole. Plans indicate to be used for second floor. Reference section 710 UPC/ State Plumbing Code(SPC.) 6. Plans missing clean-outs for branch-lines exceeding five feet. Reference section 707 UPC/ SPC. 7. Second floor building drain clean-out is required per UPC/ SPC. Revise plans. 8. Clean-outs to be installed and sized on horizontal drain per Table 7-6 UPC/SPC. 9. Pressure relief drain may not drain directly into a building drain. Revise plan to drain to an approved location. Reference section 608.5 UPC/SPC. 10. Provide gas piping layout and isometric. |
| 01/08/2003 | MARTIN HAEBERLE | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide details and size of combustion air for furnace/ HW heater room. Include calculations. 2. Provide chase detail for exhaust ducts penetrating horizontal fire assembly. 3. Provide second floor mechanical plan. 4. Condensate drain to the nearest plumbing vent is not an approved termination. Revise plans 5. Provide complete energy calculations in compliance with IECC. |
| 01/08/2003 | MARTIN HAEBERLE | WATER | REVIEW | Approved | |
| 01/15/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs to show location/method of connection to public sewer. |
| 01/22/2003 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approv-Cond | Approved with new FFE indicated on revised plan. |
| 11/20/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/20/2002 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. The Code of the Sate Board of Technical Registration ARTICLE 3. REGULATORY PROVISIONS. 32-143 Exceptions, states: A registrant under this chapter may engage in practice in another category regulated pursuant to this chapter only to the extent that the person is qualified and to the extent that the work may be necessary and incidental to the work of the registrant's profession on a specific project. This exception does not apply to public works projects. Based upon my review and in accordance with the State Board of Technical Registration Rules, this plan should be designed and sealed by an Arizona registered professional electrical engineer. 1. Small appliance branch circuits shall not serve any other loads per NEC 210-52 (b) (2). Reconfigure kitchen branch circuits. 2. Bathroom branch circuits shall not serve any other loads per NEC 210-11 (c) (3). Reconfigure bathroom branch circuits. 3. Access is hindered to the disconnect serving AC-3 Indoor Unit. Because the panel is within sight of this device, the breaker should be able to serve as the disconnect, unless the unit specifically requires a fused protection. 4. Submit lighting fixture schedules and cut sheets. Only then will it be possible to review branch circuit loading, NEC 410-8 compliance, IECC compliance, and compliance with the Lighting Ordinance. 5. Provide receptacles in master bedrooms to comply with NEC 210-52 (a) (1). 6. Countertop and outdoor receptacles shall be GFCI per NEC 210-8 (a) (3) and (6). 7. Complete the site lighting design. Conduit size, depth of conduit fill, conductor size, pole detail, etc. 8. Identify location of site receptacles and irrigation control. 9. Provide load calculation for house panel. Note that minimum ampacity of aluminum conductors for 40 A is #6, not #8 conductors. NEC Table 310-16, NEC 110-14 (c) (1). 10. Please clarify whether AC Outside Unit and AC Inside Unit are coincident loads, to enable evaluation of Service Tabulation for the panel. 11. Water Heater is 2500 VA on Service Tabulation and 4500 on Sheet P2. Correct. 12. In order to use NEC Table 220-32, all conditions in 220-32 must be met, including the use of nameplate rating of appliances. No double diversity. 13. Recalculate service loads to evaluate whether the aluminum conductors are rated to carry the current. 14. Neutral-ground bond shall not be in the gutter, but at the service disconnect, NEC 250-24 (b). 15. Bond to the grounding electrode system at the service disconnecting means, not in the downstream gutter. Grounding electrode conductor shall be run from this bond to the grounding electrode system, not from within the gutter. 16. Provide service disconnect rating, NEC 230-79. Can not evaluate downstream equipment grounding conductor. 17. Fuse the service disconnect. Feeders from disconnect are not protected. 18. Provide size and number of conductors, and conduit size, between individual meters and panel disconnects. 19. Since feeder conductors are aluminum, suitable landing lugs shall be specified for all terminations. NEC 110-14 (a). 20. No equipment ground shall be installed in conduit with service conductors. 21. Note that minimum ampacity of aluminum conductors protected at 125 A is 2/0, not 1/0 conductors. NEC Table 310-16, NEC 110-14 (c) (2). 22. Grounding electrode conductor shall be 2/0, not 1/0, with 600 kcmil conductors. 23. Equipment grounding conductor in House Panel circuit shall be #8 if aluminum, not #10. NEC Table 250-122. 24. Equipment grounding conductor in Unit Panel circuits shall be #4 if aluminum, not #6. NEC Table 250-122. 25. House Panel shows a 125 A fuse in a 60 A disconnect. Clarify. 26. Identify rating of house panel. Not on panel schedule. 27. Equipment on electrical site plan is not as depicted on the line diagram. Please clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/23/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |