Permit Number - T02CM05339
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Remove references to the IRC from the plans. The International Residential Code is not to be used on commercial buildings. Second request.
2. Provide Model Energy Code calculations for proposed addition. Reference Section 101.4 IECC 1998. Second request.
3. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC.
06/11/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide natural gas pipe sizing calculations. Include gas pressures, developed pipe lengths, and existing piping and gas loads on plans. Reference Section 1217.0, UPC 1994.
2. Show size, routing, and termination of condensate drain from new rooftop unit. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994.
07/09/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
07/14/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied Respectfully request establishing an appointment with Martin Haeberle prior to resubmittal.
1. CLARIFY PENETRATION FIRE-RATINGS, AT RATED CONSTRUCTION, PER CHAP 7 OF IBC, PROVIDE LISTINGS AND DETAILS ON DRAWINGS.
Note door assembly to be ¾ hour. Indicate on plans
2. SHOW HOW DOOR HARDWARE COMPLIES WITH IBC CHAP 10. Unable to find hardware schedule on plans
3.PROVIDE ACCESSIBLE ROUTE PER IBC SEC 1104. How is accessible route obtained from the parking facilities to the accessible entrances.
4.PROVIDE PARKING AND PASSENGER LOADING FACILITIES PER IBC SEC 1106. Include required signage

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
07/14/2003 ANGIE SHOFFSTALL REJECT SHELF Completed