Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05339
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Remove references to the IRC from the plans. The International Residential Code is not to be used on commercial buildings. Second request. 2. Provide Model Energy Code calculations for proposed addition. Reference Section 101.4 IECC 1998. Second request. 3. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC. |
| 06/11/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide natural gas pipe sizing calculations. Include gas pressures, developed pipe lengths, and existing piping and gas loads on plans. Reference Section 1217.0, UPC 1994. 2. Show size, routing, and termination of condensate drain from new rooftop unit. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994. |
| 07/09/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/14/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Respectfully request establishing an appointment with Martin Haeberle prior to resubmittal. 1. CLARIFY PENETRATION FIRE-RATINGS, AT RATED CONSTRUCTION, PER CHAP 7 OF IBC, PROVIDE LISTINGS AND DETAILS ON DRAWINGS. Note door assembly to be ¾ hour. Indicate on plans 2. SHOW HOW DOOR HARDWARE COMPLIES WITH IBC CHAP 10. Unable to find hardware schedule on plans 3.PROVIDE ACCESSIBLE ROUTE PER IBC SEC 1104. How is accessible route obtained from the parking facilities to the accessible entrances. 4.PROVIDE PARKING AND PASSENGER LOADING FACILITIES PER IBC SEC 1106. Include required signage |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/30/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 07/14/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |