Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE
Permit Number - T02CM05317
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/14/2003 | DAN CASTRO | ZONING | REVIEW | Denied | COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. CODE SECTION/ DEVELOPMENT STANDARD 1. Per Pima County Assessors Records, the site is comprised of four (4) separate tax codes. If the site is to function as one, lot combination is required. Attached is a copy of the lot combination covenant prepared by the City of Tucson, which must be signed, notarized, recorded, and a copy submitted to the Zoning Review Section prior to site plan approval. In addition to the covenant, a Pima County Assessors Tax Combination Form must be approved and a copy submitted to the Zoning Review Section for City records. If the site is to function as four separate lots, calculations (F.A.R., vehicle, bicycle, loading) for each lot must be provided and cross access agreements may be required. D.S. 2-02.2.1.A.2 2. Since there are a number of different retail uses allowed in the C-2 zone, provide as a note, the proposed principal land use for the building as it is listed under L.U.C. Sec. 2.5.4.2.B. D.S. 2-02.2.1.A.31 3. Since a DSMR has been approved for the drive-through lane, please note the case number, date of approval, modification granted, and conditions imposed under a general note. D.S. 2-02.2.1.A.38 4. Demonstrate graphically and by note, compliance with DSMR conditions 1 and 2 on the plan. If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/15/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
07/15/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |