Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T02CM05317
Parcel: 126130200

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05317
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2003 DAN CASTRO ZONING REVIEW Denied Structural plans must be approved by building plans examiner prior to Zoning sign off.
02/13/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct riser diagram 2/P1 to conform to Section 908, UPC.
2. Please cloud revisions.
02/13/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Manufacturer's data indicates that AC-4 has an EER of 9.5 at ARI conditions (ARI Standard 360). An economizer is required per Section 703.6, IECC. Revise plans.
2. Please cloud revisions.
02/28/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2003 ELAINE ROSE OUT TO CUSTOMER Completed