Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/06/2003 | DAN CASTRO | ZONING | REVIEW | Denied | Structural plans must be approved by building plans examiner prior to Zoning sign off. |
02/13/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct riser diagram 2/P1 to conform to Section 908, UPC. 2. Please cloud revisions. |
02/13/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Manufacturer's data indicates that AC-4 has an EER of 9.5 at ARI conditions (ARI Standard 360). An economizer is required per Section 703.6, IECC. Revise plans. 2. Please cloud revisions. |
02/28/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/04/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |