Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM05317
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2002 | BLANCA ESPINO | FLOODPLAIN | REVIEW | Approved | |
| 11/19/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/26/2002 | DAN CASTRO | ZONING | REVIEW | Denied | Building plans may not be approved until the site plan is approved. |
| 12/13/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/19/2002 | MARTIN HAEBERLE | WATER | REVIEW | Approved | |
| 12/19/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1.Provide panic hardware on door 100e. Reference section 1003.3.1.8 IBC 2.Provide exit sign illumination at exit door 100e. Note: Shown on architectural plan but not on electrical plan. Reference section 1003.2.10.4 IBC 3.Sheet L3 states, not for construction. Remove note from plans 4. Structural plans specify an HCA5-9 to be used, detail 204. Indicate which type is to be used. See Simpson catalog tables. 5. Provide structural calculations for steel canopy. |
| 12/19/2002 | MARTIN HAEBERLE | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Keynotes indicate smoke detector to be located on electrical drawings. Unable to locate. Please clarify. 2. Provide outside air as per energy calculations and IECC. Include details and size of hoods. 3. Energy calculations require an economizer. Economizer is not reflected on plans. Please revise plans 4. Energy Calculations require compliance statement signature of principals. Please provide signatures |
| 12/23/2002 | MARTIN HAEBERLE | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Wet venting of wash basins into water closet vent exceeds number of fixtures allowed. Reference section 908 UPC. Revise plans |
| 12/24/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/30/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |