Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T02CM05317
Parcel: 126130200

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM05317
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2002 BLANCA ESPINO FLOODPLAIN REVIEW Approved
11/19/2002 JIM EGAN FIRE REVIEW Approved
11/26/2002 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved until the site plan is approved.
12/13/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
12/19/2002 MARTIN HAEBERLE WATER REVIEW Approved
12/19/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1.Provide panic hardware on door 100e. Reference section 1003.3.1.8 IBC
2.Provide exit sign illumination at exit door 100e. Note: Shown on architectural plan but not on electrical plan. Reference section 1003.2.10.4 IBC
3.Sheet L3 states, not for construction. Remove note from plans
4. Structural plans specify an HCA5-9 to be used, detail 204. Indicate which type is to be used. See Simpson catalog tables.
5. Provide structural calculations for steel canopy.
12/19/2002 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Denied 1. Keynotes indicate smoke detector to be located on electrical drawings. Unable to locate. Please clarify.
2. Provide outside air as per energy calculations and IECC. Include details and size of hoods.
3. Energy calculations require an economizer. Economizer is not reflected on plans. Please revise plans
4. Energy Calculations require compliance statement signature of principals. Please provide signatures
12/23/2002 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied 1. Wet venting of wash basins into water closet vent exceeds number of fixtures allowed. Reference section 908 UPC. Revise plans
12/24/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/30/2002 TAMI ACHONG OUT TO CUSTOMER Completed