Permit Number: T02CM05307
Parcel: 14024073D

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T02CM05307
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/31/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
12/31/2002
Patricia Gehlen
1) This site plan may not be approved until the lot split issue is resolved (Refer to comment #2 dated 12/9/2002). The resolution of this issue will effect all calculations and the legal description on the site plan (sheet DWG A-7),
2) A FAR calculation and percent expansion calculation must be added to sheet DWG A-7. See comment 1 above,
3) The handi-cap parking space and ramp must be fully dimensioned,
4) Add a note which states that the existing and future half ROW's for Valencia are shown on sheet A-1,
5) The required and provided setbacks listed in general note 8 are incorrect. The required front setback is 26' (height of structure) from back of future curb and the required rear setback is 26' from edge of nearest travel lane. The provided rear setback is not 0 and the provided west setback is not 30. Revise for acurracy,
6) While the rail cars do not have to meet the code for NCD 65, the site plan must demonstrate compliance with the AHD. Please provide the mean sea level of the site so compliance may be verified.
12/31/2002 JAMES TATE FLOODPLAIN REVIEW Approved
12/31/2002 JIM TATE ENGINEERING REVIEW Approved
12/31/2002 JIM TATE SANITATION REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2003 CINDY AGUILAR OUT TO CUSTOMER Completed