Permit Number: T02CM05306
Parcel: 117020140

Address:
1044 N 2ND AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM05306
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2002 DAN CASTRO ZONING REVIEW Approved
11/15/2002 DAN CASTRO NPPO REVIEW Passed
11/15/2002 JAMES TATE FLOODPLAIN REVIEW Approved
11/27/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05306
11/27/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. DETAIL ALL FOOTINGS FOR THE FOLLOWING:
- POSTS
- COLUMNS

2. INDICATE LANDINGS, STEPS AND HANDRAILS----18" STEMWALL

FLOOR PLANS:

1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

2. DETAIL AND SPECIFY STAIR WIDTH (MINIMUM 36"), RISE AND RUN (MINIMUM 10" TREAD DEPTH AND 7 ¾"
MAXIMUM RISER HEIGHT PER R314), LANDING WIDTH (PER R312), HANDRAIL HEIGHTS (PER R315),
GUARDRAIL HEIGHT (PER R316) AND INTERMEDIATE RAIL SPACING (PER R316).

STRUCTURAL PLANS:

1. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- BEAM TO POST OR COLUMN -----------AT PORCH
- POST TO SLAB-----AT PORCH -----IF APPLIES

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

PLUMBING PLANS:

1. NOTE AND SPECIFY ALL PIPING MATERIALS.-----POLYBUTELENE IS NOT AN APPROVED MATERIAL

2. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS
AND SHOWERHEADS 3 GALLONS PER MINUTE.

3. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

MECHANICAL PLANS:

1. INDICATE SIZE AND LOCATION OF RETURN AIR SUPPLY



ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. PROVIDE AN EXTERIOR OUTLET AT A/C UNIT FOR SERVICE. THIS OUTLET SHALL BE GFI PROTECTED PER E3802.3.

3. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

5. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
12/02/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/05/2002 LISA LESNY OUT TO CUSTOMER Completed