Permit Number: T02CM05297
Parcel: 12710229A

Address:
603 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM05297
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2003 GERRY KOZIOL WWM REVIEW Denied Needs to build private sewer/needs JT use agreement.
02/06/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Same as comments on first submittal.
02/12/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Beams W 8x10 and angle 4x4x5/16 are not on the beam schedule, but are
on the calculations. Where do they apply on plans?

2) The bottom of the BEAM-COMPOSITE schedule is unclear, also the line
B 16 is unclear.
3) The details at the bottom of the concrete column schedule are unclear. Clarify!
4) Where are structural members RJ8, RJ7,and RJ9 shown on calcs.
5) Show on plans the FLOOR FRAMING ABOVE BASEMENT plan.
6) Are buildings 1 and 2 identicle?
7) Show on plans the location of the moment resisting frames as called out on calc`s.

2/12/03

1) Specify the spacing of the BC-1 and BC-2 beams and joists.
2) Structural wood shall be fire retardant and pressure treated.
3) Provide a detail showing the connection of the drag strut to a frame, beam, or shear
wall. ( See sheet S5.2)
4) Show on plans the location of the moment resisting frames as called out on calc`s.
02/13/2003 ANY FLOODPLAIN REVIEW Approved
02/13/2003 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Approved
02/13/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
2/13/2003
Plans may not be reviewed until all reviewers have approved the plans
02/13/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed