Permit Number: T02CM05267
Parcel: 125070950

Address:
627 N FORGEUS AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM05267
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
01/06/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
01/06/2003 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
02/03/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05267

2/3/03 627 N. FORGEUS AVE.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. DETAIL 1 ON 4 , AN 8" ANCHOR BOLT WON'T PROVIDE THE 7" OF REQUIRED EMBEDMENT INTO CONCRETE.

FLOOR PLANS:

1. DESIGNATE THE OPERABLE PORTION OF WINDOWS.

2. THE WALLS AND SOFFITS OF THE ENCLOSED SPACE UNDER STAIRS SHALL BE PROTECTED ON THE ENCLOSED
SIDE WITH ½" GYPSUM BOARD PER R314.8.

3. DETAIL AND SPECIFY STAIR WIDTH (MINIMUM 36"), RISE AND RUN (MINIMUM 10" TREAD DEPTH AND 7 ¾"
MAXIMUM RISER HEIGHT PER R314), LANDING WIDTH (PER R312), HANDRAIL HEIGHTS (PER R315),
GUARDRAIL HEIGHT (PER R316) AND INTERMEDIATE RAIL SPACING (PER R316).

4. PLEASE CLARIFY WHICH ROOF AREAS THE STAIRWAY SERVES. THOSE AREAS REQUIRE GUARDS, FORMERLY CALLED GUARDRAILS. PROVIDE A GUARD DETAIL. ALSO, SOME STRUCTURAL ELEMENTS MAY REQUIRE BEEFING-UP.

5. PROVIDE HANDRAILS AT STAIR WAY.

6. PROVIDE A CROSS SECTION OF THE FIRE PLACE.

7. PLEASE PROVIDE A LINTEL SCHEDULE.

STRUCTURAL PLANS:

1. PLEASE NOTE ON THE PLANS THAT THE POCKETED ROUND BEAMS ARE NOT TO INTERFER WITH GROUT CELLS.

2. DETAIL 3 ON 5 , PROVIDE FIRE BLOCKS AT THE CEILING LINE.

3. PROVIDE STAIRWAY CONNECTION DETAILS AND STRINGER SIZES. PRE-FABRICATED METAL STAIR SHALL
HAVE MANUFACTURER'S SPECIFICATIONS ATTACHED TO PLANS.

4. PROVIDE RAFTER SPACE VENTILATION.

ELEVATIONS:

1. PLEASE SIZE THE CANALES USED TO DRAIN THE ROOF IN THE NORTH ELEVATION.

PLUMBING PLANS:

1. ½" GAS APPEARS INADEQUATE FOR THE FURNACE.

2. IF THE NEW GAS LINE TIES INTO THE EXISTING GAS LINE , PROVIDE THE EXISTING FIXTURE DEMAND AND THE MAXIMUM DEVELOPED LENGTH.

3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH. IF THE NEW PIPING INVOLVES THE EXISTING WATER DISTRIBUTION SYSTEM, PROVIDE THE EXISTING FIXTURE DEMAND AND THE MAXIMUM DEVELOPED LENGTH.

4. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. THE LIGHT FIXTURE IN THE SHOWER IS REQUIRED TO BE LISTED AS APPROVED FOR USE IN S WET AREA

3. 3/0 COPPER IS INADE QUATE TO PROVIDE 260 AMPS

4. #6 COPPER GROUND IS INADEQUATE FOR A 260 AMP LOAD.

5. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL
RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL
HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5.

6. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.





IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES. PLEASE DELETE REFERENCE TO OTHER CODES.
02/06/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2003 LISA LESNY OUT TO CUSTOMER Completed