Permit Number: T02CM05236
Parcel: 13217141B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM05236
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2002 JAMES TATE FLOODPLAIN REVIEW Approved
11/13/2002 JIM EGAN FIRE REVIEW Approved
11/22/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide door/ hardware schedule for accessible and exit compliance.

2. Doors angled at 45 degrees require maneuvering clearance per section 404.2.4 ANSI 117.1 if closures are used. Please clarify
11/26/2002 TVALENC1 WATER REVIEW Approved
12/02/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
12/05/2002 GERRY KOZIOL WWM REVIEW Approved
12/09/2002 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied Pressure relief drain to terminate 6'' above grade. Reference section 608.5 State Plumbing Code.
12/09/2002 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Denied 1. Plans indicate percentage of outdoor intake to be used. Please specify actual opening size required.
12/11/2002 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2002 MONICA VALDEZ OUT TO CUSTOMER Completed