Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05232
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | Recalculate outside air requirements based on Section 403.2, IMC 2000. Please note that the occupant load for the worship center is 130 people, as shown on sheet A-2, not 60 people as shown on sheet MP-2. Third request. |
| 09/05/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2003 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 09/05/2003 | CINDY AGUILAR | REJECT SHELF | Completed |