Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM05232
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Recalculate outside air requirements based on Section 403.2, IMC 2000. |
| 06/24/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide end of run cleanout at mop sink, coordinate plumbing plan and waste & vent diagram. Reference Section 707.4, UPC. 2. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC. 3. Show routing and termination of excess pressure relief drain from water heater. |
| 07/01/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 07/11/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/11/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/15/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 07/15/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |