Permit Number: T02CM05232
Parcel: 12007047A

Address:
225 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05232
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Recalculate outside air requirements based on Section 403.2, IMC 2000.
06/24/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide end of run cleanout at mop sink, coordinate plumbing plan and waste & vent diagram. Reference Section 707.4, UPC.
2. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC.
3. Show routing and termination of excess pressure relief drain from water heater.
07/01/2003 PATRICIA GEHLEN ZONING REVIEW Approved
07/11/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
07/11/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2003 TAMI ACHONG OUT TO CUSTOMER Completed
07/15/2003 ANGIE SHOFFSTALL REJECT SHELF Completed