Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM05232
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/12/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/20/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 3/21/2003 Comments from the last review have not been addressed. Please provide a copy of the plans that Zoning stamped and approved on 11/26/02 for comparison purposes. |
| 03/20/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide end of run cleanout at mop sink and WC-1 in Pastor Office. Reference Section 707.4, UPC. 2. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC. 3. Connect piping to water heater per manufacturer's recommendations. 4. Terminate condensate drains in accordance with Section 307.2.1, IMC as amended by the City of Tucson. 5. Coordinate Domestic Water Schematic Diagram with detail 8/MP-2; show piping on plans. 6. Provide descriptive data for CP-1. |
| 03/20/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/20/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Confirm the ventilation for the restroom on the west side of the conference room conforms to Section 403.2, IMC 2000. 2. Show locations of outside air intake openings. Reference Section 401.5, IMC 2000. 3. Recalculate outside air requirements based on Section 403.2, IMC 2000. 4. Provide ventilation for Storage Room (1062 SF). Reference Section 401.2, IMC 2000. |
| 03/31/2003 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 04/09/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. Install maint. receptacles for mechanical equipment. |
| 04/30/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE PRIOR COMMENTS DATED 2/24/03. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/30/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
| 04/30/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |