Permit Number: T02CM05232
Parcel: 12007047A

Address:
225 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05232
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2003 JIM EGAN FIRE REVIEW Approved
01/15/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/27/2003 GERRY KOZIOL WWM REVIEW Approved
02/06/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide end of run cleanout at mop sink and WC-1 in Pastor Office. Reference Section 707.4, UPC.
2. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC.
3. Connect piping to water heater per manufacturer's recommendations.
4. Terminate condensate drains in accordance with Section 307.2.1, IMC as amended by the City of Tucson.
5. Coordinate Domestic Water Schematic Diagram with detail 8/MP-2; show piping on plans.
6. Provide descriptive data for CP-1.
02/24/2003 ASHOFFS1 BUILDING-COMMERCIAL REVIEW Needs Review Completely new sheets. Needs new workflow and review.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed