Permit Number: T02CM05157
Parcel: 112021350

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM05157
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2002 DAN CASTRO ZONING REVIEW Approved
11/06/2002 DAN CASTRO NPPO REVIEW Passed
11/06/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
12/06/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05157
12/06/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. ALL FOUNDATION HOLD-DOWNS FOR BRACED WALLS SHALL BE SPECIFIED AND LOCATED.
NOTE: PAHD42 HOLD-DOWNS CANNOT BE USED WITHIN 8" OF A CORNER AND MEET THE MIN. 1800# UPLIFT REQUIRED---------------A HPAHD22 MEETS THE REQUIREMENT

2. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING:
- POSTS-----AT PORCH
- COLUMNS-----AT PORCH

FLOOR PLANS:

1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL
AS THE LOCATIONS OF TEMPERED GLASS PER R308.4.
WINDOW "E" AT TUBS AND SHOWERS REQUIRE TEMPERED GLAZING
WINDOW "H" WITHIN 24" OF A DOOR REQUIRES TEMPERED GLAZING

2. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

STRUCTURAL PLANS:

1. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- BEAM TO POST-----AT PORCH
- POST TO SLAB-----AT PORCH

2. DETAIL ALL SHEAR CONNECTIONS FROM THE FOUNDATION TO THE ROOF PLYWOOD.
FOR INTERIOR BRACED WALLS

3. BRACED WALL #3 IF LESS THAN 8' IN LENGTH REQUIRES GWB ON BOTH SIDES

4. IF OPTIONAL REAR PORCH IS NOT INSTALLED INDICATE HEADERS AND CONNECTIONS FOR CANTILEVERED FRAMING OVER WINDOWS

5. TJI DOES NOT MFG. A 25 SERIES I-JOIST

PLUMBING PLANS:

1. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
12/10/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2002 CINDY AGUILAR OUT TO CUSTOMER Completed