Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T02CM05157
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/06/2002 | DAN CASTRO | ZONING | REVIEW | Approved | |
11/06/2002 | DAN CASTRO | NPPO | REVIEW | Passed | |
11/06/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
12/06/2002 | TERRY STEVENS | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T02CM05157 12/06/02 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. ALL FOUNDATION HOLD-DOWNS FOR BRACED WALLS SHALL BE SPECIFIED AND LOCATED. NOTE: PAHD42 HOLD-DOWNS CANNOT BE USED WITHIN 8" OF A CORNER AND MEET THE MIN. 1800# UPLIFT REQUIRED---------------A HPAHD22 MEETS THE REQUIREMENT 2. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING: - POSTS-----AT PORCH - COLUMNS-----AT PORCH FLOOR PLANS: 1. PROVIDE ALL WINDOW SIZES AND TYPES, AND DESIGNATE THE OPERABLE PORTION OF WINDOWS, AS WELL AS THE LOCATIONS OF TEMPERED GLASS PER R308.4. WINDOW "E" AT TUBS AND SHOWERS REQUIRE TEMPERED GLAZING WINDOW "H" WITHIN 24" OF A DOOR REQUIRES TEMPERED GLAZING 2. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 STRUCTURAL PLANS: 1. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING PLANS: - BEAM TO POST-----AT PORCH - POST TO SLAB-----AT PORCH 2. DETAIL ALL SHEAR CONNECTIONS FROM THE FOUNDATION TO THE ROOF PLYWOOD. FOR INTERIOR BRACED WALLS 3. BRACED WALL #3 IF LESS THAN 8' IN LENGTH REQUIRES GWB ON BOTH SIDES 4. IF OPTIONAL REAR PORCH IS NOT INSTALLED INDICATE HEADERS AND CONNECTIONS FOR CANTILEVERED FRAMING OVER WINDOWS 5. TJI DOES NOT MFG. A 25 SERIES I-JOIST PLUMBING PLANS: 1. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS @ 791-5550 EXT. 1112 |
12/10/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/11/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |