Permit Number: T02CM05114
Parcel: 128121870

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T02CM05114
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2003 GERRY KOZIOL WWM REVIEW Approved
06/25/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05114

4726 E. MOMTECITO ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



STRUCTURAL PLANS:

1. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREA. IF SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF LOWER TRUSSES. PROVIDE A PLATE OR JUSTIFY POINT LOADING ON THE EXISTING ROOF DECK.

2. 2X6 #2 D.F. @ 12" O.C. APPEARS TO BE INADEQUATE TO SPAN THE BED ROOM. PLEASE JUSTIFY.

SECTIONS - DETAILS - MISC. NOTES:

1. B-B/S3 ; PLEASE PROVIDE A PLATE ON THE EXISTING ROOF FOR THE OVER FRAMING OR JUSTIFY THE EXISTING ROOF DECK FOR POINT LOADING.

2. 3/S3 ; PLEASE JUSTIFY THIS DETAIL. I'VE SEEN IT ILLUSTRATED SOMEPLACE BUT CAN'T FIND IT. MY CONCERN IS THE 1X4 FAILING IN SHEAR ( APROX. 417# @ 35 PSF ROOF ) AND THE SINGLE PLATE SPLICES REQUIRE A PLATE CONNECTION AND RAFTERS REQUIRE 11/2" (MIN.) BEARING.

PLUMBING PLANS:

1. PLEASE REVISE THE "PLUMBING FIXTURE UNIT SCHEDULE" TO REFLECT THE U.P.C.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110


NOTE: AS OF 2-02-01 THE CITY OF TUCSON HAS ADOPTED THE 2000 IRC EXCEPT FOR THE PLUMBING PORTION WHICH IS THE STATE PLUMBING CODE. ALL MODEL PLANS SHALL BE REFERENCE TO THE PREVIOUSLY MENTIONED CODES.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2003 LISA LESNY OUT TO CUSTOMER Completed
06/26/2003 ANGIE SHOFFSTALL REJECT SHELF Completed