Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T02CM05093
Parcel: 11103207B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM05093
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2003 RSHERRY1 BUILDING-COMMERCIAL REVIEW Approved
01/31/2003 MARTIN HAEBERLE WATER REVIEW Approved
01/31/2003 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Approved
02/03/2003 TACHONG1 WWM REVIEW Passed
02/19/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Fundamentally, it does not appear from the diagram that this design meets the National Electrical Code. Per NEC 680-57 (c) a sign installed inside a fountain shall be at least 5' from the edge. Please see the attached.
2. Specify what type of GFCI is to be provided. Per NEC 680-57 (b) all circuits supplying the sign shall have ground-fault circuit-interrupter for personnel. Per NEC 680-51(a) a GFCI shall be installed in the branch circuit supplying fountain equipment.
3. Show sign disconnect per NEC 680-57 (d) and 600-6.
4. Show design for sign complies with NEC 600-9 (d).
5. Sign ballast shall conform to NEC 600-22.
6. Specify operating voltage on new equipment and existing panel.
7. Specify grounding and bonding per NEC 680-53, 680-54, and Article 250.
8. Size the circuit breaker supplying the pump and sign. Indicate number of poles.
9. Provide overheating protection for submersible pump per NEC 680-51 (d) if applicable.
10. Per NEC 680-51 (f) all equipment shall be removable from the water for normal maintenance. This is not clear from the submittal.
11. Insure stability of installed equipment per NEC 680-51 (g).
12. Provide motor disconnecting means per 430-102 (b).

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2003 ELAINE ROSE OUT TO CUSTOMER Completed