| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2002 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 11/01/2002 | HOLLY PEARCE | WATER | REVIEW | Denied | Plumbing/Water 1. Provide a complete civil site utility plan. (Plan submitted incomplete.) sealed by a civil engineer. 2. Show where the water comes from, size, etc. |
| 11/06/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Structural Plans do not indicate length of anchors for sign. Please provide 2. Provide cross-section for sign support pier and foundation. |
| 11/06/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide an electrical design with panel load, new loads,panel location,circuiting,overcurrent protection,conduit & conductor sizes,wiring method,all applicable equipment locations and all important information regarding this installation. |
| 11/08/2002 | GERRY KOZIOL | WWM | REVIEW | Denied | 1) Need more plumbing information. 2) Cannot drain backwash fountain to sewer. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/31/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |