Permit Number: T02CM05085
Parcel: 133130120

Address:
7730 E PIMA ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM05085
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2002 PATRICIA GEHLEN ZONING REVIEW Approved
11/01/2002 PATRICIA GEHLEN NPPO REVIEW Passed
11/01/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/20/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05085

11/20/02 7730 E. PIMA ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. DIMENSION THE MINIMUM WIDTH FOR THE WATER CLOSET AREA.

2. HOW DOES AN 8" HEARTH EXTENSION COMPLY WITH R1004.2 FOR A FACTORY BUILT FIRE PLACE? PLEASE PROVIDE A CROSS SECTION.

3. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

STRUCTURAL PLANS:

1. PROVIDE MANUFACTURER'S DATA SHEETS FOR PRE-FAB TRUSSES. TRUSS DATA SHEETS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA.

2. DETAIL GABLE END BRACING CONNECTIONS.

3. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.

4. SPECIFY THE BEAM SIZES FOR THE PORCH.

5. PLEASE RE-CHECK THE DOUBLE 2X6 HEADERS OVER THE 5' OPENINGS BETWEEN THE PORCH AND THE FAMILY ROOM AND THE HEADERS UNDER THE INTERMEDIATE BEAM ON THE PORCH.

6. SPECIFY WEIGHT OF ROOF SYSTEM ITEMS (IE WEIGHT OF SELECTED TILE). PROVIDE ICBO EVALUATION
REPORT NUMBER AND MANUFACTURER OF ALL FIBER GLASS-TYPE ROOFING TILES.





ELEVATIONS:

1. NOTE AND SPECIFY ALL ROOF SLOPES APPROPRIATE TO MATERIAL (SEE R905).

2. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

3. NOTE AND DIMENSION THAT THE FIREPLACE CHIMNEY MUST TERMINATE A MINIMUM OF 2' ABOVE ANY
POINT OF ROOF WITHIN 10' MEASURED HORIZONTALLY AND NOT LESS THAN 3' ABOVE THE POINT WHERE
THE CHIMNEY PASSES THROUGH THE ROOF, PER R1001.6

4. FOR VENEER, NOTE AND SPECIFY TYPE OF VENEER. PROVIDE DETAIL AND SPECIFY ANCHORING METHOD,
BACKING, VAPOR BARRIER,TIES, FLASHING, AND WEEP HOLES PER R703.7.

SECTIONS - DETAILS - MISC. NOTES:

1. A/5, PROVIDE BOTTOM PLATE TO CONCRETE CONNECTION.

2. F/5, THE MINIMUM ROOF SLOPE FOR A TILE ROOF IS 2 ½ :12 WITH A DOUBLE UNDERLAYMENT, UNLESS THE MATERIAL IS LISTED OTHERWISE.

3. G/5, PROVIDE THE TIE SPACING, FLASHING, WEATHER BARRIER, AND WEEP HOLES PER R703.7 .

PLUMBING PLANS:

1. 2 WATER FIXTURE UNITS FOR A TUB AND A SHOWER PER THE U.P.C. ALSO THE WASTE FIXTURE UNITS FOR A CLOTHES WASHER IS 2. THE PLUMBING PORTION OF THE I.R.C. HASN'T BEEN ADOPTED. PLEASE ADJUST THE FIXTURE CHART.

2. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.

ELECTRICAL PLANS:

1. IF THE TOP, EAST OF THE KITCHEN SINK, IS 12" WIDE OR WIDER, IT REQUIRES A RECEPTACLE.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
11/21/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2002 TAMI ACHONG OUT TO CUSTOMER Completed