Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM05076
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2002 | JIM EGAN | FIRE | REVIEW | Denied | 1. OCCUPANT LOAD SHOULD BE BASED ON CONCENTRATED USE..(1:7) 2. FIRE SPRINKLERS REQUIRED IN A-3 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300. 3. PANIC HARDWARE REQUIRED FOR REQUIRED EXIT DOORS FROM A OR E OCCUPANCY WITH 100 OR MORE OCCUPANTS. |
| 11/15/2002 | DAN CASTRO | ZONING | REVIEW | Passed | |
| 11/18/2002 | JIM TATE | FLOODPLAIN | REVIEW | Approved | |
| 11/29/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Clarify occupant load calculations for unconcentrated uses. See Fire plan review. 2. Provide automatic fire extinguishing system for proposed activity building per section 903.2.1.3 IBC 3. Clarify type of exiting hardware to be used as stated in the construction documents 4. The occupant load of the existing facilities used to meet the required plumbing fixtures for the activity center is to be done utilizing Table 1003.2.2.2 IBC. Please clarify 5. Provide completed Special Inspection Form prior to permit issuance. 6. Storage rooms over 100 square feet for incidental storage to have a one-hour fire barrier. Reference Table 302.1.1 IBC Revise Plans |
| 12/12/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2002 | MARTIN HAEBERLE | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/13/2002 | MARTIN HAEBERLE | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide complete energy calculations. 2. Storage area requires a one-hour fire barrier. Provide required fire dampers for proposed duct penetrations. |
| 12/13/2002 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/13/2002 | MHAEBER1 | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/16/2002 | TAMI ACHONG | OUT TO CUSTOMER | Completed |