Permit Number: T02CM05074
Parcel: 127032210

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T02CM05074
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2002 DAN CASTRO ZONING REVIEW Approved
11/01/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/01/2002 DAN CASTRO NPPO REVIEW Passed
12/09/2002 REYES ARVAYO BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05074

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.


SITE PLAN:

1. INDICATE THE LOCATION OF GAS, WATER, ELECTRIC AND SEWER LINE ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER AND GAS METER

FLOOR PLAN

1. WINDOWS WITHIN 24" OF A DOOR SHALL HAVE SAFETY GLASS.

FOUNDATION PLANS:

1. BOTTOM PLATE ANCHOR BOLTS LAYOUT AND SIZE?

2. DETAIL BOTTOM PLATE CONNECTION PER IRC TABLE R603.3.1

STRUCTURAL

1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR , ROOF DEAD LOAD AND LIVE LOAD.
2. LOAD BEARING STUDS SHALL BE DIRECTLY IN-LINE WITH RAFTERS. PER IRC 603.1.2
3. INDICATE SIZE OF METAL STUDS - MEMBER DESIGNATION. PER IRC TABLE R603.21

ELEVATIONS:

1. ELEVATION DOESN'T MATCH FLOOR PLAN ON 2'8" CORNER BRACE PANELD??

MECHANICAL PLANS:

1. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.6. INDICATE LOCATION OF BASE BOARD HEATERS

ELECTRICAL PLANS:

1. NOTE ON DRAWINGS THAT ALL EXISTING BEDROOMS AND COMMON AREAS MUST HAVE SMOKE ALARMS- BATTERY OPERATED OK.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
REYES ARVAYO @ 791-5550 EXT. 1113

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2002 TAMI ACHONG OUT TO CUSTOMER Completed