Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM05067
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
11/01/2002 PETER MCLAUGHLIN NPPO REVIEW Passed
11/01/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/18/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM05067

11/18/02 2825 E. LA MADERA #2

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FOUNDATION PLANS:

1. PLEASE CHECK THE DIMENSION LINES. THEIR MAY BE AN ERROR ON THE LEFT SIDE.

STRUCTURAL PLANS:

1. JUSTIFY THE LINTEL AND HEADER SCHEDULES FOR THE MOST HEAVILY LOADED WALL OR SPECIFY FOR SPECIFIC OPENINGS.

2. PROVIDE MANUFACTURER'S DATA SHEETS FOR THE PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA.

ELEVATIONS:

1. PLEASE SHOW THE LOCATIONS OF THE CANALES.

2. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREAS PER R903.4.

SECTIONS - DETAILS - MISC. NOTES:

1. 1/7, PLEASE SIZE THE CANALES.

2. 1/7, 2/7, THE LEDGER BOLT SIZES AND SPACINGS CONFLICT WITH FIGURE R606.10(1) IN THE I.R.C. .

3. 1/7, 2/7, FOOTING DETAIL, AN 8" BLOCK WALL REQUIRES AN 8" STEM WALL.


PLUMBING PLANS:

1. WATER LINE AND GAS LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH OF THE FIXTURES IN THE EXISTING RESIDENCE.




MECHANICAL PLANS:

1. PLEASE SIZE THE RETURN AIR.

2. TWO COMBUSTION AIR GRILLS ARE REQUIRED AT THE WATER HEATER.

ELECTRICAL PLANS:

1. THE RECEPTACLE AT THE PENINSULAR TOP CAN'T BE LOCATED UNDER THE OVER HANG OF THE TOP IF THE TOP OVER HANGS MORE THAN 6".

2. THE 1½" CONDUIT FEEDING THE EXISTING 100 AMP PANEL,WON'T ACCOMMODATE 3-4/0 CONDUCTORS.

3. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.




IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
11/21/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2002 LISA LESNY OUT TO CUSTOMER Completed