Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Permit Number - T02CM05002
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 03/10/2003 | PETER MCLAUGHLIN | NPPO | REVIEW | Passed | |
| 03/10/2003 | PGILBER1 | FLOODPLAIN | REVIEW | Approved | |
| 03/26/2003 | GP | BUILDING-RESIDENTIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet SD1 Please show the location of all site utilities. Sheet A1 1. References in the schedules to A/A2 and B/A2 were not found. Please clarify. 2. Window type 4, as shown in the east bath, requires safety glazing. Ref. R308.4.4. 3. The master bedroom windows do not provide the 8% glazing requirement referenced in R303.1. The french doors may provide the additional 12.9 s.f. required. Please specify the dimensions of the glazing in the french doors and note that safety glazing will be provided for these side hinged doors. Ref. R308.4.1. 4. Please indicate the wall type at the west wall of the second bedroom along the Meyer St. frontage. It also appears that window type 5 occurs in two locations at this wall. Please clarify. 5. Please specify safety glazing for the shower enclosure doors. Ref. 308.4.4. 6. Please provide a listed assembly reference number or an item number from IBC Table 719.1(2) for the dwelling separation wall. Ref. R321.1. 7. Provide the ICBO report number for the fireplace and detail per R1004. Sheet A6 8. Specify roof ventilation provisions. Ref. R806. STRUCTURAL COMMENTS Sheet S1 9. Please specify the special inspection requirement for high strength concrete. Ref. IBC 1704.4. 10. Show the sleeving for the underground conduits that will occur at the kitchen areas. 11. Please correct the allowable soil bearing pressure note. Ref. Table 404.4.1. 12. The lateral load wind speed note should reflect the 90 MPH 3 second gust factor for the City of Tucson. 13. Show the landings at the exterior doors. Ref. R312.1.2. Sheet S2 14. Provide two copies of the engineered truss drawings prepared by an Arizona P.E. PLUMBING COMMENTS Sheet P1 15. Penetrations in the fire resistive rated exterior walls shall be protected in accordance with R321.3. 16. Specify backflow prevention provisions for the hose bibbs. Ref. UPC 603. 17. Specify BTU/HR demands per outlet and developed length for gas pipe sizing. Ref. UPC 1217. MECHANICAL COMMENTS Sheet M1 18. Please specify elevation of ignition source at the water heater location. Ref. M1307.3. 19. Specify condensate disposal provisions. Ref. M1411.3. ELECTRICAL COMMENTS Sheet E1 20. Penetrations in the fire resistive rated exterior walls shall be protected in accordance with R321.3. 21. Specify grounding electrode conductor size. Ref. Table E3503.1. 22. Note 19th St. panel as >B= in accordance with the riser diagram. 23. The dryer appears to be electric. Please verify the nameplate rating to determine if the 20 amp circuit provided is adequate. 24. Additional convenience receptacles are required. Please see redlines. Ref. E3501.2.2. 25. Note the garage receptacles to have ground fault circuit interrupter protection. Ref. E3802.2. 26. Show the smoke alarms in each sleeping room and outside each sleeping area in the immediate vicinity of the bedrooms. Ref. R317. 27. Circuit 19B is shown as a spare in the panel schedule. This circuit has been used for the garage door opener and light. Please revise the schedule. 28. Note that the kitchen counter top receptacles will have ground fault circuit interrupter protection. Ref. E3802.6. 29. Note that the lighting in the wet / damp locations will be suitable for the locations specified. Ref. E3903.8. 30. Please identify circuits for courtyard lighting. See redlines. 31. Circuits 2 and 4 on panel A have been mislabeled. Please revise. 32. Circuit 9A does not appear to have been used. Please revise panel schedule. 33. Counter receptacle 26A has been mislabeled. See redlines. Please revise. ENERGY COMMENTS - The energy portion has been reviewed and approved. |
| 03/26/2003 | EROSE1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/26/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |