Permit Number: T02CM04983
Parcel: Unknown

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD

Permit Number - T02CM04983
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
10/28/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
11/08/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM04983
11/08/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. DIMENSION THE DEPTH INTO UNDISTURBED SOIL FOR EACH FOOTING TYPE AND CONDITION PER TABLE R403.1.--------------MIN. 12" BELOW NATURAL GRADE WHICH WOULD BE BELOW GRANULAR FILL

STRUCTURAL PLANS:

1. DOUBLE 2X8 BOX BEAM SPANNING 16' FOR PLANT LEDGE IS INADEQUATE. CHANGE OR SUBMIT CALCS.

2. LEDGER CONNECTIONS PORCH TO WALL INADEQUATE WITH 12d NAILS. PROVIDE POSITIVE CONNECTION REQUIRED. LAGS, CLIPS, ETC.-------ALSO 2X4 LEDGERS AT PLANT LEDGE

3. HANGER TYPES AND SIZES FOR RAFTERS MISSING AT PORCH AND PLANT LEDGE LEDGERS.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.---------ASPHALT SHINGLES REQUIRE A VENTED ATTIC SPACE

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
11/08/2002 PETER MCLAUGHLIN NPPO REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2002 TAMI ACHONG OUT TO CUSTOMER Completed