Permit Number: T02CM04968
Parcel: 134220030

Address:
6606 E LEHIGH DR

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM04968
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
10/25/2002 PETER MCLAUGHLIN ZONING REVIEW Passed
10/28/2002 JIM EGAN FIRE REVIEW Approved
10/29/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. Provide the manufactures name and listing for the drain funnel. NOTE: This will be a tripping hazard outside of the building. Provide a trap primer for any floor sink. 2. Vent on the grease trap shall be down stream of the trap, provide a clean out down stream. 3. Provide a screen for the roof and overflow drains.
10/29/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Model energy code calculations are not with the plan set. 2. Show on the plan how the mechanical design complies with Chapter 4 IMC2000. 3. Provide a better and complete detail of the work required in #5 and #6 of 3M3.3.
10/29/2002 HOLLY PEARCE WATER REVIEW Approved
11/08/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Please complete and submit Special Inspection Certificate

2. Door 1002 has been indicated as an exit door. Therefore, the ramp is part of the egress system. Provide a landing at door 1002 as per section 1003.3.1.5 IBC.

3. Please clarify if egress door 1002 is the accessible exit per section 1003.2.13 IBC. Revise plans to reflect compliance with ANSI A117.1.

4. Egress ramp at door 1002 is not to have a slope steeper than 8%. Reference section 1003.3.4.1 IBC.

5. Provide cross section of the proposed handrails for existing stairs indicating compliance with sections 1003.3.3.11 thru 1003.3.3.11.5 IBC.

6. Provide handrails for each side of the stairs as per section 1003.3.3.11 IBC.
11/15/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
11/22/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2002 CINDY AGUILAR OUT TO CUSTOMER Completed