Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM04929
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/23/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/23/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/23/2002 | HOLLY PEARCE | WATER | REVIEW | Passed | |
| 10/23/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 11/06/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Structural Calculations indicate the use of 4,000 psf for allowable foundation pressure. Maximum allowed bearing pressure to be used without a soils report is 1500 psf. Submit revised calculations or provide a soils report justifying proposed bearing pressures. |
| 11/08/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/10/2002 | CRAIG GROSS | ZONING | REVIEW | Approved | |
| 12/10/2002 | SEPTIC APPROVAL | WWM | REVIEW | Approved | Exiting septic shall have 100 ft setback to any well. No new waste plumbing. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/16/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |