Permit Number: T02CM04811
Parcel: 103090190

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T02CM04811
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2002 JIM EGAN FIRE REVIEW Denied 1. FIRE SPRINKLERS REQUIRED. INDICATE SO ON CODE REVIEW CHECKLIST.
2. PROVIDE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLANS:
a. Standard to be used.
b. Hazard Classification
c. Minimum design density and area of application.
d. Water Supply Info. Static psi, residual psi, flow gpm.
10/29/2002 HOLLY PEARCE WATER REVIEW Approved
10/29/2002 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
11/01/2002 GERRY KOZIOL WWM REVIEW Denied Need to use agreement. 11/01/2002
11/04/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
11/04/2002
Copies of the stamped approved site and landscape plans must be included in the submittal package prior to review.
11/05/2002 JAMES TATE FLOODPLAIN REVIEW Denied A copy of the stamped approved site plan must be included with the submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2002 DELMA ROBEY OUT TO CUSTOMER Completed