Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T02CM04811
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/29/2002 | JIM EGAN | FIRE | REVIEW | Denied | 1. FIRE SPRINKLERS REQUIRED. INDICATE SO ON CODE REVIEW CHECKLIST. 2. PROVIDE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLANS: a. Standard to be used. b. Hazard Classification c. Minimum design density and area of application. d. Water Supply Info. Static psi, residual psi, flow gpm. |
| 10/29/2002 | HOLLY PEARCE | WATER | REVIEW | Approved | |
| 10/29/2002 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
| 11/01/2002 | GERRY KOZIOL | WWM | REVIEW | Denied | Need to use agreement. 11/01/2002 |
| 11/04/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 11/04/2002 Copies of the stamped approved site and landscape plans must be included in the submittal package prior to review. |
| 11/05/2002 | JAMES TATE | FLOODPLAIN | REVIEW | Denied | A copy of the stamped approved site plan must be included with the submittal. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/06/2002 | DELMA ROBEY | OUT TO CUSTOMER | Completed |