Permit Number: T02CM04766
Parcel: 104092210

Address:
4187 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM04766
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .... T02CM04766 ......4187 N. ORACLE ROAD .. DGL 12/6/02 1. SEE PRIOR COMMENT #6 : ( 6. PROVIDE MANUFACTURER'S NAME AND MODEL NUMBER FOR CEILING, REF. NOTE #3 ON DWG. A3.0 OR FULLY DETAIL INCLUDING WIRE TIE AND CONNECTIONS TO EXISTING, etc. , REF. 3/A7.1. ).
12/26/2002 MARTIN HAEBERLE MECHANICAL-COMMERCIAL REVIEW Approved
12/26/2002 MARTIN HAEBERLE PLUMBING-COMMERCIAL REVIEW Denied Number of fixtures serving the grease trap exceeds allowed amount per section 1011.4 UPC/ State Plumbing Code.
Provide a grease interceptor and include sizing calculations per Appendix H.
12/26/2002 MARTIN HAEBERLE WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2003 CINDY AGUILAR OUT TO CUSTOMER Completed