Review Details: COMMERCIAL TI

Permit Number - T02CM04766
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2002 JIM EGAN FIRE REVIEW Approved
10/14/2002 ANY FLOODPLAIN REVIEW Approved
10/14/2002 DAVID RIVERA ZONING REVIEW Approved
10/15/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing UPC1994Az.Code being used. 1. Provide a complete waste line ismetric drawing of all new waste lines. 2. Provide four RPPB assm. for P-106, 107, 109 and 110. 3.Provide condensate lines, size and discharge location on the plans.
10/15/2002 HOLLY PEARCE WATER REVIEW Denied Plumbing plans will need to be replaced.
10/15/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical IMC2000 being used. 1.Provide the manufactures name and listing for the Type I hoods on the plans. 2. Detail 12/A7.1 is incorrect and incomplete. A one hour ceiling is required over and 18" around all sides of the hoods. Shaft enclosure shall be one hour per IBC2000. NOTE: 6" of air space is required between the duct and shaft wall.
10/31/2002 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied ..T02CM04766 ....4187 N. ORACLE ROAD ...DGL ...10/31/02 1. PROVIDE CONNECTION AND BRACING DETAILS, INCLUDING FASTENERS W/ TYPE, SIZE SPACING/ NUMBER, REF. DETAIL 10/A7.0 . . ................................. .. 2. PROVIDE STRUCTURAL CALCULATIONS FOR NEW PARAPETS, REF. DETAILS 10/ A7.1, 11/ A7.1, BY STRUCTURAL ENGINEER W/ SEALED AND SIGNED DRAWINGS AND CALCULATIONS. ............ ... .... .... .... 3. PROVIDE STRUCTURAL DETAILS AND DESIGN CALCULATIONS FOR EXHAUST HOOD 12/ A7.1. ............. .. 4. FULLY DETAIL AND DOCUMENT OPTION/S AT CHASE 12/ A7.1, REF. IBC, PROVIDE COPY OF LISTING FOR FIRE-RATING ON DRAWINGS. . ................................ ..... . 5. CLAIRFY DOOR SWING AT DOOR BETWEEN ROOM #108 AND ROOM #107, SWING IN DIRECTION OF EGRESS TO EXTERIOR EXIT DOOR FROM ROOM # 108. . ......... . ... 6. PROVIDE MANUFACTURER'S NAME AND MODEL NUMBER FOR CEILING, REF. NOTE #3 ON DWG. A3.0 OR FULLY DETAIL INCLUDING WIRE TIE AND CONNECTIONS TO EXISTING, etc. , REF. 3/A7.1. . .. ... ....... ............. ... .. 7. SHOW ADDRESS ON BUILDING ELEVATION/S PER PIMA COUNTY ADDRESSING ORDINANCE , SEE ATTACHMENT, REF. A5.0 , A5.1. . ................... .......... . ...
11/01/2002 GERRY KOZIOL WWM REVIEW Approved
11/04/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2002 DELMA ROBEY OUT TO CUSTOMER Completed