Permit Number: T02CM04760
Parcel: 133110010

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM04760
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2002 JIM EGAN FIRE REVIEW Approved
10/21/2002 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved by the Zoning Review Section until the site plan is approved by all sections.
10/25/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide Structural Calculations for cloud structure. See Sheet A3.6

2. Indicate wall glass assemblies to have a maximum of ¾" deflection per Chapter 24 IBC

3. Provide exit width calculations for exiting at hall 100. Include existing building in calculations.

4. Door at hall 100 encroaches into width of exit door. Clarify encroachment meets minimum width requirements per sections 1003.2.3.1.1 and 1003.3.1.1 of the IBC.

5. Provide handrail extensions for ramps at classrooms in corridor 104. Reference section 1003.2.1.3 IBC

6. Provide accessible means of egress from stage.If lift is to be used please detail on plans. Reference section 1003.2.1.3 IBC

7. Egress door at kitchen does not meet approach criteria reflected in Figure 404.2.4.1 ANSI 117.1. Revise plans

8. Provide occupant load calculations. Include total occupants to utilize plumbing fixtures as per Table 2902.1 IBC

9. Provide a typical detail for the mounting of accessible signs.

10. The hardware schedule within the project manual appears to be incomplete. Please specify on the door schedule doors to have panic hardware. Include doors that may be utilizing the "Main Exit" exception. Reference section 1003.3.1.8 IBC.

11. The two-hour firewall utilized for separation of buildings does not comply with the vertical continuity requirements of the IBC. Revise plans or provide allowable area calculations, including the existing building, showing compliance with the total area allowed. Reference section 705.6 IBC

12. Please clarify that skylight specifications reflect compliance with section 2405 IBC.

13. Note 53 on sheet A2.1 conflicts with design for one-hour fire barrier wall. Please clarify

14. A-3 to B occupancies requires a two-hour separation. Reference Table 302.3.3 IBC. Please address on plans
10/28/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Denied Plumbing 1. A backwater valve will not be required, FFE= 34.6 and the MH Rim= 33.76. Remove detail 9/P2.1.
10/28/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied Mechanical 1. Provide a smoke detector in the return air Per Sec 606.2.1 IMC2000. 2. Provide a Type-I hood over the range Per Sec 507.2 IMC2000. 3. The exaust fan in the game room does not comply with Sec 101.2 IECC 1998.
11/12/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
11/13/2002 HOLLY PEARCE WATER REVIEW Approved
11/15/2002 GERRY KOZIOL WWM REVIEW Approved
11/18/2002 ANY FLOODPLAIN REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2002 MONICA VALDEZ OUT TO CUSTOMER Completed