Permit Number: T02CM04630
Parcel: 123111630

Review Status: Completed

Review Details: REVISION

Permit Number - T02CM04630
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
05/07/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/15/2003 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM04630
05/15/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. A ONE HOUR FIRE WALL IS REQUIRED BETWEEN UNITS. 5/8" TYPE GWB ON BOTH SIDES OF A FRAME WALL WHICH EXTENDS FROM THE SLAB TO BOTTOM OF ROOF DECK IS REQUIRED. PROVIDE DETAIL OF FIRE WALL

ELECTRICAL PLANS:

1. INDICATE SIZE OF FEEDERS AND CONDUIT TO EXISTING PANEL

2. DESIGNATE THE LOCATION AND CIRCUIT OF ALL REQUIRED LIGHT FIXTURES, RECEPTACLE OUTLETS, POWER
OUTLETS AND SWITCHES. PROVIDE A PANEL SCHEDULE NOTING CIRCUIT NUMBER AND SIZE ALONG WITH A
GENERAL DESCRIPTION.

3. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.

4. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL
RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL
HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5.

5. NOTE THAT AT LEAST ONE 20-AMP BRANCH CIRCUIT SHALL BE INSTALLED TO SERVE THE LAUNDRY ROOM,
AND THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS, PER E33603.3 AND 3801.8.

6. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

7. SUBMIT PANEL SCHEDULE SHOWING CIRCUIT AMPACITY, WIRE SIZES, PANEL SIZE AND CIRCUIT NUMBERS.

8. EXISTING WIRING INDICATED MUST BE REWIRED TO NEW SERVICE INDICATED

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2003 TAMI ACHONG OUT TO CUSTOMER Completed