| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2002 | JIM EGAN | FIRE | REVIEW | Denied | 1. PROVIDE COMPLETE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN. 2. MINIMUM CLASS 1 STANDPIPE REQUIRED IN EACH STAIRWELL WITH HOSE OUTLETS PROVIDED ON EACH FLOOR LEVEL AND THE ROOF. SPECIFY TYPE OF STANDPIPE SYTEM PROVIDED AND INDICATE LOCATION OF STANDPIPE/HOSE OUTLETS ON PLAN. SEE 2000 IFC SECTION 905. |
| 11/18/2002 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
| 11/21/2002 | GLENN HITZ | WWM | REVIEW | Denied | Needs wastewater review of private sewer W/GWH (need to construct @ right angle to Craycroft Road). Needs to build private sewer. Needs to permit private sewer with DEQ. Needs copy of private sewer for Base Map update. Needs manhole tap permit. GWH 11-21-02 |
| 11/22/2002 | ANY | FLOODPLAIN | REVIEW | Approved | |
| 11/22/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 11/22/02 copies of the landscape and NPPO plans with the development plan approval stamp must be inserted into each set of the building plans prior to approval. |
| 11/26/2002 | MSTPAUL1 | WATER | REVIEW | Approved |