Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T02CM04617
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2002 JIM EGAN FIRE REVIEW Denied 1. PROVIDE COMPLETE FIRE SPRINKLER SYSTEM DESIGN CRITERIA ON PLAN.
2. MINIMUM CLASS 1 STANDPIPE REQUIRED IN EACH STAIRWELL WITH HOSE OUTLETS PROVIDED ON EACH FLOOR LEVEL AND THE ROOF. SPECIFY TYPE OF STANDPIPE SYTEM PROVIDED AND INDICATE LOCATION OF STANDPIPE/HOSE OUTLETS ON PLAN. SEE 2000 IFC SECTION 905.
11/18/2002 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
11/21/2002 GLENN HITZ WWM REVIEW Denied Needs wastewater review of private sewer W/GWH (need to construct @ right angle to Craycroft Road). Needs to build private sewer. Needs to permit private sewer with DEQ. Needs copy of private sewer for Base Map update. Needs manhole tap permit. GWH 11-21-02
11/22/2002 ANY FLOODPLAIN REVIEW Approved
11/22/2002 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
11/22/02
copies of the landscape and NPPO plans with the development plan approval stamp must be inserted into each set of the building plans prior to approval.
11/26/2002 MSTPAUL1 WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2002 DELMA ROBEY OUT TO CUSTOMER Completed