Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T02CM04576
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/26/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide methods of penetration protection of firewall. References section 711 IBC. See roof drains 2. A five-foot clearance around the water closet is required. References section 604.3 A117.1 ANSI. Revise plans Lavatory is not allowed to encroach into the required space. 3. One-hour firewall to have integrity maintained from foundation through parapet. See section A sheet A02. References section 705.6 IBC. Clarify on plans. See roof drains |
| 03/15/2004 | DOUG WILLIAMS | ENGINEERING | REVIEW | Approved | |
| 03/16/2004 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 03/17/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | See 8th floor for review of sewer easement. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/18/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 03/18/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |