Permit Number: T02CM04576
Parcel: 120082440

Address:
4718 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM04576
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Approved
02/26/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide methods of penetration protection of firewall. References section 711 IBC. See roof drains
2. A five-foot clearance around the water closet is required. References section 604.3 A117.1 ANSI. Revise plans Lavatory is not allowed to encroach into the required space.
3. One-hour firewall to have integrity maintained from foundation through parapet. See section A sheet A02. References section 705.6 IBC. Clarify on plans. See roof drains
03/15/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved
03/16/2004 DAVID RIVERA ZONING REVIEW Approved
03/17/2004 GERRY KOZIOL WWM REVIEW Denied See 8th floor for review of sewer easement.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2004 LISA LESNY OUT TO CUSTOMER Completed
03/18/2004 ANGIE SHOFFSTALL REJECT SHELF Completed