Permit Number: T02CM04576
Parcel: 120082440

Address:
4718 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T02CM04576
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2004 GERRY KOZIOL WWM REVIEW Denied Needs wastewater credit evaluation.
C.O. over public sewer?
Combined lots between an alley? Needs to abandon alley?
Needs Wastewater review of existing public sewer easement.
12/08/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Approved
12/08/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Modify waste riser diagram to conform to Section 908.0, UPC. Note: The riser diagram shows the horizontal waste line from a lavatory connecting to the vent of a water closet, a violation of Section 311.4, UPC 1994. The trap arm of the lavatory may share the vent of the water closet if the section of the water closet vent below the junction of the trap arm and the water closet vent (a vertical wet vent, Section 908.0, UPC 1994) is increased in size to 3". The length of the trap arm is limited by Table 10-1, UPC 1994.
2. Modify the size of the vent through the roof to conform to Section 904.1, UPC. Note: Two 2" vents have a combined cross-sectional area of 6.8 square inches; a 3" waste line (the minimum size required by Table 7-5) has a cross-sectional area of 7.4 square inches.
3. Provide a backwater valve in the building drain (the upstream manhole rim elevation is higher than the first floor elevation of the building). Reference Section 710.1, UPC 1994.
12/12/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
12/23/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied Building plans may not be approved prior to Site Plan approval.
12/31/2003 DAVID RIVERA ZONING REVIEW Denied Zoning will approve the building plans after the plans have been approved by the structural reviewers.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2004 LISA LESNY OUT TO CUSTOMER Completed
01/15/2004 ANGIE SHOFFSTALL REJECT SHELF Completed