Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM04565
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2002 PETER MCLAUGHLIN ZONING REVIEW Approved
09/30/2002 PETER MCLAUGHLIN NPPO REVIEW Passed
09/30/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
10/30/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM04565

10/30/02 859 W. MONTANA ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FLOOR PLANS:

1. SHOW WHICH ROOMS EXIST ADJACENT TO THEADDITIONS AND THEIR EXTERIOR DOORS AND WINDOWS.

STRUCTURAL PLANS:

1. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS DATA MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

2. PROVIDE 2'-8"MINIMUM WIDTH BRACED WALL PANELS (SHEAR WALLS) AT EACH END OF THE NORTH WALL OF THE PORCH AND THEIR HOLD- DOWNS.

PLUMBING PLANS:

1. NOTE ON PLANS THAT TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

MECHANICAL PLANS:

1. HOW WILL THE ADDITIONS BE HEATED?



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
10/31/2002 GERRY KOZIOL WWM REVIEW Approved