Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM04542
Parcel: 14108521C

Review Status: Completed

Review Details: SITE

Permit Number - T02CM04542
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2002 JIM EGAN FIRE REVIEW Denied FIRE HYDRANTS REQUIRED. SUBMIT APPROVED COT WATER PLAN.
10/10/2002 DAN CASTRO HANDICAP-SITE REVIEW Approved
10/10/2002 DAN CASTRO ZONING REVIEW Approved
10/16/2002 ANY SANITATION REVIEW Approved See engineering folder.
10/16/2002 PAUL MACHADO ENGINEERING REVIEW Approved To: James R. Watson Architect 5672 E. Kelso St.
Tucson, Arizona 85712


SUBJECT: Century Park Research Center, Bldg. No. 4, ph. 4
Site plan T02CM04542 (First Review)
T15S, R15E, Section 18


RESUBMITTAL REQUIRED: None



Site Plan:

The site plan is approved.


If you have any questions, I can be reached at 791-5550 or pmachad2@ci.tucson.az.us

Paul Machado
Senior Engineering Associate,
10/16/2002 ANY FLOODPLAIN REVIEW Approved See engineering folder.
10/21/2002 JOE LINVILLE LANDSCAPE REVIEW Denied Based on the proposed expansion the provisions of LUC 3.7 apply to the entire site. Submit landscape plans that demonstrate code compliance for all areas of Lot 19. References to previously approved plans are not acceptable.
Locations of existing protected native plants to be preserved are to be shown on the revised plan. See also NPPO comments.

A minimum of one canopy tree must be located within the vehicular use area. LUC 3.7.2
10/21/2002 JOE LINVILLE NPPO REVIEW Denied Based on the proposed expansion the requirements of LUC 3.8 apply to the proposed expansion area and the remaining undeveloped site area.

Provide a plan that documents the locations of each preserved or transplanted protected native plant per the previuosly approved plan. Revise the landscape plan as necessary.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2002 LISA LESNY OUT TO CUSTOMER Completed