Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM04451
Parcel: 110113610

Address:
2480 N SWAN RD

Review Status: Completed

Review Details: REVISION

Permit Number - T02CM04451
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS:

Sheet D1

1. The revision letter identifies a demolition opening in the CMU wall for new walk-up pharmacy window. However, that does not appear on the drawing. Please review and coordinate. Reference IBC Section 106.1.1.

Sheet F1 and F2

1. The revision letter identifies no changes made. However, the drawings have been revised 07 March 03. Please review and coordinate. Reference IBC Section 106.1.1.

STRUCTURAL COMMENTS:

Sheet S1

1. This drawing has not been changed and should be identified on the revision letter. Reference IBC Section 106.1.1.

PLUMBING COMMENTS:

Sheet MP1

1. The revision letter identifies removal of floor sinks. However, the drawing does not indicate a current revision. Please review and coordinate. Reference IBC Section 106.1.1.

MECHANICAL COMMENTS:

No comment.

ELECTRICAL COMMENTS:

Sheets E1 and E2

1. The revision letter identifies no charges. However, the drawings indicate revisions. Please review and coordinate. Reference IBC Section 106.1.1.

Sheet E2.1

1. The drawing indicates a current revision. However, the revision letter does not identify any changes. Please review and coordinate. Reference IBC Section 106.1.1.

Sheet E3

1. The revision letter identifies changes. However, the drawing does not indicate a current revision. Please review and coordinate. Reference IBC Section 106.1.1.

2. The revision letter indicates additional receptacles and lights. However, Sheet E3 is the electrical one-line diagram. Please provide the total number of additional switches, receptacles, and light fixtures added for the current electrical revision, and coordinate upon which drawing that is shown. Reference IBC Section 106.1.1.

ENERGY CODE COMMENTS:

No comment.

ACCESSIBILITY COMMENTS:

No comment.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed