Permit Number: T02CM04450
Parcel: 126080290

Address:
4106 E 5TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM04450
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2002 DAVID RIVERA ZONING REVIEW Approved
09/23/2002 DAVID RIVERA NPPO REVIEW Passed
09/23/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
10/10/2002 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM04450

10/10/02 4106 E. 5TH ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.



FOUNDATION PLANS:


1. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1:

19" MINIMUM; 4" BRICK VENEER OVER LIGHT FRAME CONSTRUCTION

2. PROVIDE AN ANCHOR BOLT DETAIL FOR THE BRACED WALL PANELS. (SEE R602.10.6)


STRUCTURAL PLANS:

1. IF UNDER THE ROOF OVER FRAMING, SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.).

2. PROVIDE CONNECTION DETAILS FOR THE VALLEY BEAM TO THE LEDGER AND TO THE WALL.

3. PROVIDE CONNECTION DETAILS FOR THE EAST END OF THE TWO GLUE LAMS OVER THE NEW HALL, BETWEEN THE EXISTING BEDROOM AND THE BATHROOM, TO THE BEARING.

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE VENEER DETAILS TO REFLECT R703.7, ETC. (i.e. SUPPORT, ANCHORAGE, TIES @ WALL OPENINGS, AIR SPACE, FLASHING, WEEP HOLES, AND WEATHER RESISTIVE BARRIER )

PLUMBING PLANS:

1. PLEASE CLARIFY PLUMBING NOTE 12. BOTH SHHOWER AND TUB/SHOWER COMBINATIONS TO HAVE INDIVIDUAL CONTROL VALVES OF THEPRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE. SEE THE '94 U.P.C. SECTION 410.7 .


ELECTRICAL PLANS:

1. PROVIDE A RECEPTACLE IN THE HALL BEHIND THE WATER CLOSET.

2. PLEASE NOTE THE LIGHT IN THE SHOWER IS TO BE LISTED AS BEING APPROVED FOR USE IN A WET AREA.

3. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE
DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3. ( ARE THEY EXISTING? )

4. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

5. PLEASE NOTE THE EXISTING RESIDENCE IS TO BE EQUIPPED WITH SMOKE DETECTORS. ( SEE R317.1.1 )



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
10/14/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2002 DELMA ROBEY OUT TO CUSTOMER Completed