10/02/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM04349
10/02/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. INDICATE THE LOCATION OF ELECTRIC LINES ON THE PROPERTY AND WHERE THEY ENTER THE BUILDING.

FOUNDATION PLANS:

1. PROVIDE SEPARATE FOUNDATION PLAN.

2. INDICATE MIN. DEPTH OF FOOTING INTO NATURAL GRADE [ 12"] AND MIN. CLEARANCE FROM NATURAL GRADE TO SILL PLATE OR POST [ 8"]

3. FOOTING WIDTHS FOR ONE-STORY, PER TABLE R403.1:
- 16" MINIMUM; WOOD FRAME

4. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING:
- INTERIOR BEARING WALLS---MIN. 12" INTO NATURAL GRADE AND 16" WIDE

5. LOCATE AND SPECIFY ALL ANCHOR BOLT SPACING ON THE FOUNDATION PLAN.

STRUCTURAL PLANS:

1. PROVIDE COMPLETE ROOF FRAMING PLANS. SHOW SIZE, SPACING AND SPAN OF ALL FRAMING MEMBERS, TRUSSES, JOISTS, RAFTERS, BEAMS, GLULAMS, LINTELS, HEADERS, LEDGERS AND BLOCKING.

2. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS INCLUDING:
- I-JOISTS TO TOP PLATE--------POSITIVE CONNECTION MISSING
- BEAM TO CORBEL AT PORCH POST
- SILL TO SLAB, ANCHOR BOLT SIZES AND SPACING
- LEDGERS TO FRAME--------INDICATE SPACING OF LAGS

3. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. NOTE AND SPECIFY THE SIZE, SPACING AND LENGTH OF ANCHOR BOLTS FOR SILL PLATES, TOP PLATES AND
LEDGERS.

PLUMBING PLANS:

1. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

2. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE, BTU DEMAND OF EACH APPLIANCE, SIZE OF
EACH BRANCH, TOTAL DEMAND & TOTAL DEVELOPED LENGTH FROM METER TO MOST REMOTE
APPLIANCE ON THE SYSTEM PER UPC 1217.2

3. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH

4. NOTE ON PLANS THAT SHOWER AND TUB / SHOWER COMBINATIONS THAT HAVE INDIVIDUAL CONTROL
VALVES SHALL BE OF THE PRESSURE BALANCE OR THERMOSTATIC MIXING VALVE TYPE.

5. AS PER 1994 UPC SECTION 509 THE WATER HEATER CANNOT BE LOCATED IN BATHROOM

6. PROVIDE PLAN VIEW OF WASTE LINES

MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.-------ONE 6X18 DUCT DOES NOT MEET CODE

2. INDICATE SIZE AND LOCATION OF SUPPLY AND RETURN DUCTS

ELECTRICAL PLANS:

1. NOTE THE GROUNDING AND BONDING METHOD OF THE SUB PANEL.

2. INDICATE SIZE OF FEEDERS TO THE SUBPANEL

3. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS.

4. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
10/03/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
10/03/2002 PATRICIA GEHLEN ZONING REVIEW Approved
10/03/2002 PATRICIA GEHLEN NPPO REVIEW Passed
10/07/2002 GERRY KOZIOL WWM REVIEW Denied Needs design review of lift station.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2002 CINDY AGUILAR OUT TO CUSTOMER Completed