Permit Number: T02CM04112
Parcel: 125012090

Address:
2820 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T02CM04112
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
09/09/2002 DAVID RIVERA ZONING REVIEW Approved
09/11/2002 JIM EGAN FIRE REVIEW Denied MINIMUM ONE HOUR RATED FIRE BARRIER WALL REQUIRED BETWEEN NEW CARPORT AND EXISTING LAUNDRY BUILDING.
09/12/2002 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Passed
09/25/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide cross-section for 1 hour fire barrier wall required for separation between the B and U occupancies. Reference section 302.2.3 IBC 2000.

2. On site plan indicate with the limit of fire barrier wall.

3. Plans reflect design and special inspection criteria as per 97 UBC. Revise plan to reflect IBC 2000.

4. Indicate proximity of proposed structure to property lines. Note: if less than 5 feet provide plans and details to indicate compliance with Table 602 IBC 2000

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2002 CINDY AGUILAR OUT TO CUSTOMER Completed