Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T02CM04112
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2002 | DOUG WILLIAMS | FLOODPLAIN | REVIEW | Approved | |
| 09/09/2002 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/11/2002 | JIM EGAN | FIRE | REVIEW | Denied | MINIMUM ONE HOUR RATED FIRE BARRIER WALL REQUIRED BETWEEN NEW CARPORT AND EXISTING LAUNDRY BUILDING. |
| 09/12/2002 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 09/25/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide cross-section for 1 hour fire barrier wall required for separation between the B and U occupancies. Reference section 302.2.3 IBC 2000. 2. On site plan indicate with the limit of fire barrier wall. 3. Plans reflect design and special inspection criteria as per 97 UBC. Revise plan to reflect IBC 2000. 4. Indicate proximity of proposed structure to property lines. Note: if less than 5 feet provide plans and details to indicate compliance with Table 602 IBC 2000 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/27/2002 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |