02/13/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS


1) Specify on calc`s the correct code being used. (2000 IBC)
2) What do the labels or titles after Mb mean or represent-shown on 2nd page of calc`s.
3) On 3rd page of calc`s is shown C1,2,3….etc. what do they mean?
4) Highlight the worst condition used in the design.
5) Number all the sheets in the calc`s.
6) Is the 3' measured from the property line to the corner of the garage? Clarify!

2/13/03
1) Specify the allowable values of all connectors being used. (metal screws, bolts, anchor bolts, self-tapping screws, etc.) See attached sheet.
2) Show how lateral shear is being resisted and being transferred from the roof diaphragm to the walls and then to the foundation.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2003 ELAINE ROSE OUT TO CUSTOMER Stop