Permit Number: T02CM04077
Parcel: 12003009B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T02CM04077
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2002 PATRICIA GEHLEN ZONING REVIEW Approved
08/28/2002 PATRICIA GEHLEN NPPO REVIEW Passed
08/28/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
09/10/2002 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T02CM04077----------09/10/02
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:
1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FOUNDATION PLANS:

1. INTERIOR BEARING FOOTING MISSING AT WALL BETWEEN MASTER BEDROOM AND WATER CLOSET ROOM

2. DIMENSION THE DEPTH INTO UNDISTURBED SOIL FOR EACH FOOTING TYPE AND CONDITION PER TABLE R403.1.---------DETAILS 2,3,4 OF 2.-----ALSO 6" CLEARANCE FROM NATURAL GRADE TO SILL DETAIL

STRUCTURAL PLANS:

1. SPECIFY LUMBER GRADE AND SPECIES. 6X8 BEAM AT REAR PORCH IS OVERSPANNED IF IT IS DF#2 SPECIFY IF BEAM IS TO BE DF#1

2. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- BEAM TO POST------TYPE OF CONNECTION MISSING, DETAILS 5/6 & 7/6
- LEDGER TO BEAM----POSITIVE CONNECTION MISSING, DETAIL 5/6
- I-JOIST TO LEDGER-----INDICATE TYPE AND SIZE OF HANGERS
- DETAIL 8/6 &10/6-----LU38 IS NOT MFG'D. & WOULD NOT WORK WITH 2X FRAMING OF PORCHES
- STRAPS AND BEAM SEAT-----INDICATE TYPE AND SIZE AT DETAILS 9/6 AND 11/6

3. NOTE AND DETAIL TIE STRAPS FRAMING ANCHORS AND JOIST HANGERS BY TYPE, SIZE AND REQUIRED
ATTACHMENT TO FRAMING MEMBERS.

PLUMBING PLANS:

1. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH BASED ON THE 1994 UPC WITH STATE AMENDMENTS NOT THE IRC 2000

2. FYI------THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

MECHANICAL PLANS:

1. NOTE ON PLANS: MECHANICAL SHALL COMPLY WITH CHAPTERS 12 -16 AND18- 24 2000 IRC.
NOTE: CHAPTER 17 OF THE IRC 2000 HAS NOT BEEN ADOPTED. COMB. & RELIEF REQUIREMENTS ARE IN THE 1994 UPC WITH STATE AMENDMENTS--------CHANGE NOTES

ELECTRICAL PLANS:

1. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
MUST BE WITHIN 36" OF EACH BASIN

MODEL ENERGY CODE:

1. PLEASE PROVIDE TWO COPIES OF ENERGY CALCULATIONS

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
09/13/2002 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/17/2002 LISA LESNY OUT TO CUSTOMER Completed