Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T02CM04055
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2002 | PATRICIA GEHLEN | ZONING | REVIEW | Passed | |
| 09/26/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/26/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1. Provide the size of the existing sewer and the total fixture units on the same. 2. Architect of record to provide a detail of the roof overflow drain-- detail 2-A9.0. |
| 09/26/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. The use of weather hoods does not comply with Sec 101.2 IECC 1998. |
| 09/26/2002 | HOLLY PEARCE | WATER | REVIEW | Approved | |
| 10/02/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide pre-engineered building plans and calculations. Note: insure axial load transfer for seismic and winds are provided per detail 201. 2. Provide a code analysis utilizing the 2000 IBC. Include the additional structures proposed. 3. The proposed work is located on three different sites. Provide two complete sets of plans for each site. 4. Provide the minimum number of plumbing facilities for the activity buildings as per Table 2902.1 IBC. 5. As per the code analysis provided door #9 of the kitchen addition will be part of the egress system. The maximum width of the door may not exceed 48". Reference section 1003.3.1.1 IBC. Revise size of door 6. Indicate hardware proposed for door #9 within the kitchen addition. |
| 10/07/2002 | EROSE1 | WWM | REVIEW | Approved | |
| 10/08/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/17/2002 | PAUL MACHADO | FLOODPLAIN | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/18/2002 | ELAINE ROSE | OUT TO CUSTOMER | Approved |