Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T02CM04053
Parcel: 20914001C

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T02CM04053
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2002 PATRICIA GEHLEN ZONING REVIEW Passed
10/09/2002 JIM EGAN FIRE REVIEW Approved
10/09/2002 DOUG WILLIAMS FLOODPLAIN REVIEW Approved
10/15/2002 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Passed
10/15/2002 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Passed
10/15/2002 HOLLY PEARCE WATER REVIEW Passed
10/17/2002 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Mezzanine exceeds the maximum allowed 75' travel distance without two exits being provided. Reference section 505.3 IBC. Relocate exit door or provide two exits from the mezzanine.
2. Plans do not reflect the required landing for the exit door. Reference section 1003.3.1.5 IBC. Please incorporate the required landing on plans
3. Two different size mezzanines are indicated on plans. Please clarify
4. Guardrails for balcony do not provide opening limitations as required per section 1003.2.12.2 IBC. Revise plans
5. Mezzanine does not indicate guards as required by section 1003.2.12 IBC. Please incorporate into plans.
6. Structural calculations where submitted for the foundation only. Please submit calculations for the building including the design for the guardrails and stairs. Reference load criteria for stairs and guards as per table 1607.1 and sections 1607.7.1 through 1607.7.3 of the IBC
7. Exterior walls less than 30' from the property line are required to have a fire resistive rating of 2 hours. Reference section 412.2 IBC. Clarify actual property lines and spatial separation of neighboring areas/ structures.
10/25/2002 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Approved
11/06/2002 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2002 TAMI ACHONG OUT TO CUSTOMER Completed