| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2002 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/09/2002 | RANDY SCHULER | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/20/2002 | HOLLY PEARCE | PLUMBING-COMMERCIAL | REVIEW | Denied | Plumbing 1.Provide FFE, MH Rim Elev.,size, slope of sewer on C104. 2. Roof overflow drain requires a screen like the roof drain- A601. 3. Roof and overflow drains can not be connected together, Sheet P101. |
| 09/20/2002 | HOLLY PEARCE | MECHANICAL-COMMERCIAL | REVIEW | Denied | Mechanical 1. MEC Calc's have incorrect figures in the heating degree days and cooling degree days. 2. Show on the plan how the mechanical design complies with Chapter 4 IMC 2000. 3. Show on the plan how access is made to the equipment on any upper roofs or wells. |
| 09/20/2002 | HOLLY PEARCE | WATER | REVIEW | Approved | |
| 09/24/2002 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Sheet S601 Provide hangar type to be used referenced in details 203 and 206. Sheet A102 Exit gates required to serve as means of egress for the buildings served. Reference sections 1003.22.10 and 1003.3.2.2 IBC. Provide occupant loads served including existing buildings serving the yard area. Plans to reflect egress requirements for exit doors. |
| 10/24/2002 | ELIZABETH EBERBACH | FLOODPLAIN | REVIEW | Denied | 1) Floodplain Use Permit shall be obtained. 2) A copy of the stamped approved Site Plan shall be submitted with the building plan set. 3) see T02BU02343 for comments. |
| 11/18/2002 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | See site plan comments for Zoning. |
| 11/19/2002 | GERRY KOZIOL | WWM | REVIEW | Approved |